Shunt/Bypass UL 924 Emergency Lighting Relays

Tech Tuesday Blog Banner

Functional Devices offers UL 924 Emergency Lighting Relays listed for controlling lights on an Emergency lighting circuit. The Automatic Load Control Relay (ALCR) versions are very popular (see the ESRN device). However, what if a simpler UL 924 device could be used to shunt or bypass a local electrical switch for Emergency lighting control? For such applications, we offer the slimmed-down, 20A contact rated, ESR2401B or ESR2402B as a good starting point.

SHUNT/BYPASS APPLICATION

When Normal Power is present, the ESR Bypass/Shunt relay coil is activated (Contacts N/O), and the emergency panel is fed from Normal Power. The lighting load can be switched on/off using an individual wall switch. When normal power drops out, the ESR coil is deactivated and N/C contact falls closed.

Shunt/Bypass Application

If there is already a local wall switch or other means of controlling power to an Emergency light, then the ESR2401B could be used to force the light on if Normal power drops out. The ESR2401B is for a feed of 120Vac Normal power. If there is a feed of 277Vac Normal power, use the ESR2402B model.

Now, what about applications where there is 0-10Vdc dimming and the light needs to be forced to full brightness if Normal power drops? The ESR2401B or ESR2402B may still be used and wiring it up would look like the diagram below.

DIMMING OVERRIDE LOW VOLTAGE APPLICATION

When Normal Power is present, the ESR coil is activated and the N/O contacts are closed, allowing for the 0-10 Vdc to control the dimming of the load. When Normal Power is lost, the N/O contacts open, breaking the 0-10 Vdc dimming control, bringing the light load to full brightness.

Dimming Override Low Voltage Application

We also offer double-pole, double-throw (DPDT) versions in both 10A contact rating and 20A contact rating. Please see those options in the table below:

MODEL NORMAL/UTILITY VOLTAGE INPUT CONTACT RATING
ESR2401D 120Vac 10A
ESR2402D 208-277Vac 10A
ESR01P 120Vac 20A
ESR02P 208-277Vac 20A

When it comes to UL 924 applications of controlling Emergency lighting, you may not need a full ALCR device. Using the shunt/bypass options detailed in this blog may be wise, as the installation will be simpler and more cost effective. The results are savings in time and money. Be sure, though, that a UL 924 device for shunt/bypass is appropriate for your application.

Do you have any technical questions? Give us a call and ask for Tech Support or send in a support email - we're happy to help!

Confidence and Peace of Mind

Functional Devices, Inc., located in the United States of America, has been designing and manufacturing quality electronic devices since 1969. Our mission is to enhance lives in buildings and beyond. We do so by designing and manufacturing reliable, high-quality products for the building automation industry.  Our suite of product offerings include RIB relays, current sensors, power controls, power supplies, transformers, lighting controls, and more.